Please use this identifier to cite or link to this item: https://publication.npru.ac.th/jspui/handle/123456789/895
Title: The Secondary Transmission Lines Defining and Ranking to Support Power Transfer and Proper Dispatch for Power System Control
การกำหนดและจัดลำดับสายส่งรองเพื่อรองรับการส่งผ่านกำลังไฟฟ้าและการสั่งการ ที่เหมาะสมสำหรับการควบคุมระบบไฟฟ้ากำลัง
Authors: Wannoi, Chaisit
Wannoi, Narumon
ชัยสิทธิ์ วันน้อย
นฤมล วันน้อย
Keywords: ranking
secondary transmission line
power transfer
dispatch
power system control
Issue Date: 9-Jul-2020
Publisher: Nakhon Pathom Rajabhat University
Citation: C. Chompoo-inwai, C. Yingvivatanapong, P. Faungfoo and W.J. Lee, “Transmission Congestion Management during Transition Period of Electricity Deregulation in Thailand”, IEEE Transaction on Industrial Application, vol. 43, issue 6, Nov –Dec 2007, page(s): 1483 – 1490.
T. Mandloi1, A. K. Jain, a study of power system security and contingency analysis, International Journal of Scientific Research Engineering & Technology (IJSRET), Volume 3, Issue 4, July 2014.
A. A. Abdulrazzaq, “Contingency ranking of power systems using a performance index”, International Research Journal of Engineering and Technology (IRJET), Vol.2, May, 2015.
C. Wannoi, S. Bunjongjit and C. Chompooinwai, “A Proper Location FACTS Device Placement and Primary Generation Response Definition for Multi-Lines Buses Security Enhancement under Contingency Analysis”, International Conference on Electrical Engineering, 2015.
C. Wannoi, N. Wannoi, C. Boonkhun, C. Temiyasathit and C. Chompoo-inwai, “A Novel Transmission Line’s ATC Assessment Method by Considering the Generation Dispatch Limit (GDL) and Renewable Generation Capacity with Power Flow Sensitivity Analysis”, International Journal of Intelligent Engineering and Systems, Vol.12, No.5, 2019, pp.179-189.
Energy Policy and planning office ministry of energy, “Thailand Power development plan 2018” A. Sadiq and M. Nwohu, “Evaluation of Inter – Area Available Transfer Capability of Nigeria 330KV Network”, International Journal of Engineering and Technology, Vol.3 No.2, 2013.
North American Electric Reliability Council (NERC), “Available Transfer Capability Definitions and Determination”, NERC Report, 1996.
Abstract: This paper presents the secondary transmission lines defining and ranking to support power transfer and proper dispatch for power system control with power flow sensitivity analysis. The power sensitivity analysis in this paper has considered the Line Outage Distribution Factor (LODF) to rank the secondary transmission line. For, a proper dispatch has considered the Available Transfer Capability (ATC) of the secondary transmission lines by considering the thermal limit. In this study has focused the secondary transmission lines defining and ranking for inter tied-lines and used a modified Thailand power system as the base system. A modified Thailand power system is divided into 7 sub-systems connected with 27 inter tied-lines. The study results show that if these inter tied-lines are outage, it will make the secondary transmission lines receive an additional load which it cause power congestion problem in the system. The study results can define and point out the power distribution routes through the secondary transmission lines. These power distribution data can be used to rank the secondary transmission lines for proper dispatch planning in power system control.
บทความนี้นำเสนอการกำหนดและจัดลำดับสายส่งรองเพื่อรองรับการส่งผ่านกำลังไฟฟ้าและการสั่งการที่เหมาะสม สำหรับการควบคุมระบบไฟฟ้ากำลังด้วยการวิเคราะห์ความไวกำลังไฟฟ้าไหล การวิเคราะห์ความไวกำลังไฟฟ้าในบทความนี้จะ พิจารณาค่าแฟคเตอร์การกระจายกำลังไฟฟ้าหลังสายส่งถูกปลดออกเพื่อจัดลำดับสายส่งรอง สำหรับการสั่งการที่เหมาะสม ของระบบจะพิจารณาจากความสามารถส่งผ่านพลังงานพร้อมมูลของสายส่งรองโดยพิจารณาค่าจำกัดด้านความร้อนของสาย ส่ง ในการศึกษานี้ได้มุ่งเน้นศึกษาการกำหนดและจัดลำดับสายส่งรองสำหรับสายส่งเชื่อมต่อระหว่างพื้นที่และได้ใช้ระบบไฟฟ้า กำลังปรับปรุงประเทศไทยเป็นระบบฐาน ซึ่งระบบไฟฟ้ากำลังประเทศไทยได้แบ่งออกเป็น 7 ระบบย่อย โดยมีสายส่งเชื่อมต่อ ระหว่างพื้นที่ 27 สายส่ง ผลการศึกษาพบว่าหากสายส่งเหล่านี้หากถูกปลดออกจะส่งผลให้เกิดปัญหาความหนาแน่นพลังงาน ขึ้นในระบบจากการที่กลุ่มสายส่งรองได้รับภาระโหลดเพิ่มขึ้น และผลการศึกษาสามารถกำหนดและชี้ให้เห็นถึงเส้นทางการ กระจายกำลังไฟฟ้าผ่านสายส่งรองเส้นต่างๆ ซึ่งข้อมูลการกระจายกำลังไฟฟ้าเหล่านี้สามารถนำมาจัดลำดับสายส่งรองเพื่อใช้ ในการวางแผนสำหรับการสั่งการที่เหมาะสมในการควบคุมระบบไฟฟ้ากำลัง
URI: https://publication.npru.ac.th/jspui/handle/123456789/895
Appears in Collections:Proceedings of the 12th NPRU National Academic Conference

Files in This Item:
File Description SizeFormat 
7.pdf667.97 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.